British Standard Cables
Position:Home > Products > Cable series > British Standard Cables- Specification
- Description
- Download
Cable Construction
Anealed copper conductor
Stranding to BS 6360 CL-5 or IEC 60228 CL-5
- PVC core insulation TI 4 to EN 50363-3-1(formerly BS 7655-3-1)
- Green/Yellow grounding (3 conductors and above)
- PVC outer jacket Type 10 to BS7655-4-2
- Yellow or blue
Application and Description
318A to BS 6004(Formerly BS 7919) cables are designed to withstand severe external temperatures and will remain flexible at temperatures down to -40°C. Making them particularly suitable for outdoor applications and for use where flexibility is required at sub zero temperatures. At normal temperatures the cable is very flexible, offering some of the characteristics usually found in elastomeric cables.,
Technical Characteristics
Working voltage: 300/500 volts
Test voltage: 2000 volts
Flexing bending radius: 6xOverall diameter
Static bending radius: 4xOverall diameter
Flexing temperature: -5º C to +70º C
Static temperature: -40º C to +70º C
Short circuit temperature: +160º C
Flame retardant: IEC 60332.1
- Insulation resistance: 20 MΩxkm