6181X/6182X/6183X/6184X/6185X to BS 7889
Specification
Description
Download

Cable Construction

图片1.png图片2.png

Bare copper conductor

Stranding to BS 6360 CL-2 or IEC 60228 CL-2

XLPE GP8 insulation

Inner covering (optional)

PVC sheath Type 9 to BS7655-4.2


Application and Description

6181X/6182X/6183X/6184X/6185X to BS 7889 cables are designed for surface wiring where there is little risk of mechanical damage and are suitable for use in electrical installations such as power and lighting.


Technical Characteristics

Working voltage: 600/1000V

Minimum bending radius: OD<25 mm : 4xoverall diameter,

Operating temperature: -150C to +900C

Insulation resistance: 10 Mohm / km

Flame retardant: IEC 60332.1