Language

British Standard Cables

Position:Home > Products > Cable series > British Standard Cables
6491B to BS 7211 (New BS EN 50525-3-41)
Specification
Description
Download

Cable Construction

图片1.png图片2.png

Bare copper made of solid/strands conductor

Solid to BS 6360 CL-1 or IEC 60228 CL-1(H07Z-U)

Stranding to BS 6360 CL-2 or IEC 60228 CL-2(H07Z-R)

Stranding to BS 6360 CL-5 or IEC 60228 CL-5(H07Z-K)

LSOH thermosetting core insulation type EI5


Application and Description

6491B to BS 7211 (New BS EN 50525-3-41 cables are designed for fixed wiring purposes in domestic and industrial power/lighting applications. They can be used in trunking or conduit, or may be surface mounted when used for earthing. And 6491B to BS 7211 (New BS EN 50525-3-41) cables are generally in areas (such as public and government buildings) where smoke and toxic fumes may cause a threat to life and equipment. 6491B to BS 7211 (New BS EN 50525-3-41) cables produce no corrosive gasses when burnt and which is particularly important where electronic equipment is installed. 6491B is equivalent to harmonized code H07Z-U/ H07Z-R/H07Z-K.


Technical Characteristics

Working voltage: 450/750 volts

Test voltage: 2500 volts

Minimum bending radius:

up to 10 mm2 - 3xoverall diameter,

above 25 mm2 - 6xoverall diameter

Operating temperature: +00 C to +900 C

Short circuit temperature: +2500 C

Insulation resistance: 10 MΩxkm

Halogen free acc. to EN 50267-2-1 / IEC 60754-1

Smoke density acc. to EN 50268-2 / IEC 61034-2

Corrosivity of gases acc. to EN 50267-2-2, IEC 60754-2

Flame retardancy  acc. to EN 50265-2-1, IEC 60332-1