Language

Harmonized Code PVC cables

Position:Home > Products > Cable series > Harmonized Code PVC cables
H05V2-U & H07V2-U
Specification
Description
Download

Cable Construction

图片1.png图片2.png

Solid bare copper single wire
Solid to DIN VDE 0281-3, HD 21.3 S3 and IEC 60227-3
Special PVC TI3 ore insulation
Cores to VDE-0293 colors on chart
H05V-U (20, 18 & 17 AWG)
H07V-U (16 AWG and Larger)


Application and Description
H05V2-U/H07V2-U cables are for fixed protected installation inside appliances and in, or on, lighting fittings. Suitable for installation in surface mounted or embedded conduits, only for signalling and control circuits. Maximum conductor temperature in normal use 90°C. Not to be used in contact with object higher then 85°C. Not suitable for fixed distribution system.


Technical Characteristics

Working voltage: 300/500v (H05V-U)
Working voltage: 450/750v (H07V-U)
Test voltage: 2000V(H05V-U)/2500V (H07V-U)
Flexing bending radius: 15 x Ø
Static bending radius: 15 x Ø
Flexing temperature: -5º C to +70º C
Static temperature: -30º C to +80º C
Short circuit temperature: +160º C
Flame retardant: IEC 60332.1
Insulation resistance: 10 MΩ x km